In today’s digitally dependent world, even a split-second power failure can cause data loss, hardware damage, and business disruption. Whether you are running a data center, a corporate server room, or a sensitive industrial control system, a reliable True Online UPS is critical. Indo Powersys Pvt. Ltd., a trusted name in Indian power solutions, introduces the IP Series – a high-frequency, double-conversion True Online UPS designed for critical applications ranging from 1KVA to 3KVA.
Let’s explore how this intelligent UPS series delivers uninterrupted, clean, and efficient power to safeguard your business-critical operations.
Key Features of Indo Powersys IP Series UPS (1KVA–3KVA)
This IP Series UPS system is designed using advanced DSP-controlled double conversion technology, ensuring 100% isolation between input and output, regardless of fluctuations or outages in the mains power supply. Here are its most notable features:
- True Double Conversion Online Technology: Ensures constant voltage and frequency regulation by converting incoming AC to DC and back to AC, offering pure power output regardless of input anomalies.
- High-Frequency IGBT Technology: Incorporates IGBT (Insulated Gate Bipolar Transistor) in both inverter and rectifier stages, enhancing switching performance and reducing power loss.
- Fully Digital Microprocessor Control: Advanced DSP (Digital Signal Processor) architecture ensures high-speed monitoring and instant corrective responses.
- Wide Input Voltage Range: Operates efficiently within 110–300VAC, adapting automatically to input fluctuations without switching to battery, thus extending battery life.
- High Input Power Factor (0.99): Minimizes energy losses and enhances power quality by drawing sinusoidal input current, making it energy efficient and utility-friendly.
- Up to 91% Efficiency: One of the most energy-efficient systems in its class, reducing electricity bills and heat output.
- Advanced Battery Management: Includes features like cold start, charging in UPS OFF mode, and fast recovery from deep discharge. Supports both inbuilt and long-run battery configurations.
- Comprehensive LCD Display: Real-time display of input/output voltage, frequency, load percentage, battery status, operation mode, and fault notifications.
- Smart Communication Options: Equipped with RS232 and optional SNMP for remote monitoring, real-time alerts, and graceful auto shutdown of connected systems.
- Compliant with Global Standards: Fulfills major international certifications like ISO 9001, 14001, 27001, and conforms to IEC/EN 62040 & CE/RoHS directives.
Applications
The IP Series UPS from Indo Powersys is purpose-built for mission-critical and high-sensitivity environments:
- Data Centers & Server Rooms
- Telecom Base Stations
- IT and Networking Equipment
- Banking & ATM Enclosures
- Industrial Control Panels
- CCTV and Security Systems
- Medical Labs & Diagnostic Equipment
Technical Specifications Overview
Model | IP110L3 | IP1102L6 | IP1103L6 | IP1103L8 (Long Run) |
Capacity (VA) | 1000 | 2000 | 3000 | 3000 |
Output Power Factor | 0.8 | 0.8 | 0.8 | 0.8 |
Input Voltage Range | 110–300VAC (load-based) | |||
Frequency Range | 45–55Hz (50Hz); 54–66Hz (60Hz) | |||
Input Power Factor | >0.99 | |||
Output Voltage | 220/230/240VAC ±2% | |||
Waveform | True Sine Wave | |||
Crest Factor | 03:01 | |||
Efficiency | >91% | |||
Transfer Time | 0 ms (AC to Battery), 4 ms (AC to Bypass) | |||
Battery Voltage | 36V | 72V | 96V | 96V |
Battery Configuration | 3, 6, or 8 x 12V/7Ah SMF VRLA | |||
Recharge Time | 8 hours (to 90%) | |||
Charge Current (Std./Long Run) | 1A / 6A | |||
Noise Level | <45dB | |||
Altitude | <1500m | |||
Communication | RS232, SNMP (optional), Dry Contacts | |||
Protection | Overload, Short Circuit, Overcharge, Overheat | |||
Standards | IEC/EN 62040, IS 16242:2014, RoHS |
Display & Indicator Functions
- LCD Display: Shows real-time data on voltage, frequency, battery levels, load %, temperature, and faults.
- LED Indicators:
- Green: Normal Operation
- Amber: Battery Mode
- Yellow: Warning
- Red: Fault Condition
Physical & Environmental Specs
Model | Standard Unit (kg) | Long Run Unit (kg) | Dimension (WxDxH) |
IP110L3 | 14 / 16 | – | 144 x 421 x 215 mm |
IP1103L8 | – | 34 / 36 | 191 x 478 x 339 mm |
- Operating Temp: 0°C – 40°C
- Storage Temp: -25°C – 55°C
- Humidity: 0–95% RH (Non-condensing)
Benefits at a Glance
- No Transfer Delay – Ensures continuous operation during power loss.
- Smart Charging – Keeps batteries healthy and ready for next outage.
- Advanced Safety – Inbuilt surge, overload, and short circuit protection.
- Eco-Friendly – RoHS compliant and energy efficient.
- Customizable Runtime – Add external batteries for extended backup.
Frequently Asked Questions (FAQ)
Q1: What is a True Online UPS and how is it different from Line Interactive UPS?
A: A True Online UPS uses double-conversion to provide isolated, stable, and pure power regardless of input conditions. Unlike Line Interactive UPS, it has zero transfer time, ideal for sensitive and critical equipment.
Q2: Can I use the IP Series UPS with my server setup?
A: Absolutely. It is specifically designed for servers, networking gear, and industrial applications where uninterrupted and clean power is essential.
Q3: How long does the battery last during a power cut?
A: It offers 8–16 minutes backup at 50% load using inbuilt batteries. However, the IP1103B8 model supports external batteries for longer backup, even up to several hours.
Q4: Is SNMP monitoring supported?
A: Yes. The UPS comes with RS232 communication by default and an optional SNMP slot for real-time remote monitoring and alerts.
Q5: How does the system respond to overload or short circuit?
A: It automatically shifts to bypass mode:
- 110% Load: Bypass in 30 seconds
- 150% Load: Bypass in 300ms
- This prevents hardware damage and ensures system safety.
Q6: Can I monitor the UPS parameters without a PC?
A: Yes. The LCD panel provides real-time visibility of all operational parameters, battery condition, and fault status.
Q7: What type of batteries are used?
A: The UPS uses Sealed Maintenance-Free (SMF), VRLA batteries, which are safe, compact, and don’t require any user maintenance.
Q8: How often should I replace the batteries?
A: Typically, batteries last 2–3 years, depending on usage and ambient temperature. Regular maintenance checks are recommended.
Q9: Is the UPS compatible with generators?
A: Yes. The wide input voltage/frequency range allows it to work seamlessly with generator power, making it perfect for extended power outages.
Q10: Where can I buy or get technical support?
A: Contact Indo Powersys at:
- J-1249, Phase III, Sitapura Industrial Area, Jaipur-22
- 0141-2771421 / 2771422
- info@ips2k.com | indopowersys@gmail.com
- ips2k.com